29
WARNING
Before any connections are made to the generator, make sure that the main circuit
breaker and the Control Power switch are in the OFF (O) position and that the negative
(-) battery cable is disconnected. Potentially lethal voltages may be present at the
generator connection lugs.
IMPROPER OR INCORRECT CONNECTIONS TO A BUILDING’S ELECTRICAL SYSTEM
CAN CAUSE POTENTIALLY LETHAL VOLTAGE TO BACKFEED INTO UTILITY LINES.
THIS MAY RESULT IN INJURY OR ELECTROCUTION TO UTILITY WORKERS NEARBY.
MAKE SURE THE GENERATOR IS SUPPLYING POWER TO AN ISOLATED OBJECT
OR BUILDING THAT IS NOT CONNECTED TO ANY UTILITY LINES.
Connections should be made by plugging power cables equipped with series 16 taper nose 400A/600V cam lock
plugs into the cam lock receptacles. Secure the connection by rotating the plug a 1/2 turn to the right.
WARNING
NEVER attempt to disable or modify the lug door safety switches. Equipment damage,
personal injury or death may result.
A ground connection is located on the far right of the cam lock panel. The unit MUST be connected to a good earthen
ground for proper operating safety. The generator neutral is bonded to ground when it is shipped from the factory.
The bonding plate will need to be removed when the generator is used as a standby power source. INSTALLATION
SHOULD BE IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE (NEC), STATE AND LOCAL
REGULATIONS.
WARNING
Some units are equipped with two sets of cam lock connections. Make sure all
connections to the cam lock receptacles are made to one side only, below each
corresponding breaker. i.e. DO NOT attach L1, L2 and L3 to the left side and Neutral
and Ground to the right side.
VOLTAGE SELECTOR SWITCH
The voltage selector switch mechanically changes the connections between the generator output leads and the
connection lugs on the main control panel. Voltage ranges are selected by rotating the handle on the switch to the
desired voltage.
NEVER change the voltage selector switch while the engine is running or the controller is
on. If the engine is running or starts while the setting is changed, severe arcing will occur
causing damage to the switch and generator windings.
The voltage selector switch is equipped with a lockout mechanism. Once the proper voltage has been selected,
insert a padlock through the lockout hole(s). By locking the handle in place, unauthorized changing of the voltage
L1
L2
L3
N (Neutral)
G (Ground)
Black
Red
Blue
White
Green
CAM LOCK PANEL
00451